OMR karta - IN.11

OMR karta IN.11

IN.11 - 8x Analogue/digital input

The A/D inputs plug-in card for control/measurement of the OMR 700 is fully isolated from the internal bus.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.
 

  • 8x Analogue/digital input
  • range: 0…30 / 120 / 250 V, ±30 / ±120 / ±250 V

Input
[ ??? ]
Number of inputs
8 inputs
DC
Range
0…30 V
>1 MOhm
0…120 V
>1 MOhm
0…250 V
>1 MOhm
±30 V
>1 MOhm
±120 V
>1 MOhm
±250 V
>1 MOhm
PM
Range
AC
Range
0…30 V
< 1 MOhm
0…120 V
< 1 MOhm
0…250 V
< 1 MOhm
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
1 % of range (DC)
5 % of range (AC)
Rate
< 1000 measur./s (DC)
< 5 measur./s (AC)
Overload capacity
2x; 10x (t < 30 ms) - ne pro > 200 V
Digital filters
floating mean
from 2…30 measurements
exponential mean
from 2…100 measurements
Functions
Tare
designed to reset display on non-zero input signal
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Power supply
Power supply
interní sběrnice 3,3 VDC,24 VDC
Current draw
< 0,75 W
Mechanical properties
Dimensions
65 x 98 mm
Installation
plug-in card
Operating conditions
Connection
connector terminal board, cable section < 2,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and inputs
Insulation resistance
for polution degree II, measuring cat. III.
input, bus
300 V (ZI), 150 V (Di)*
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
Images
Connection

User manuals

File nameFile typeVersionLanguageDownload
Návod OMR700_IN11
Operating instrucitons OMR700_IN11
PDF
2019.2
Download
Show all ↓Hide ↑