OMR karta - IN.04

OMR karta IN.04

IN.04 - 4x Input for termocouples

Plug-in card for measuring termocouple sensors is fully isolated from the internal bus with a galvanic isolation also between individual outputs.
The design of the cards allows their use at any position in the device. If during the use of the device appear new requirements to increase the number of inputs or outputs, just order another card and insert it into a free slot. In this manner the device can "grow" with your requirements.

 

  • 4x Analogue input, isolated
  • range: J/K/T/E/B/S/R/N/L

Input
[ ??? ]
Number of inputs
4 inputs, isolated
T/C
Type
selecmenu selectable
J (Fe-CuNi)
-200°…900°C
K (NiCr-Ni)
-200°…1 300°C
T (Cu-CuNi)
-200°…400°C
E (NiCr-CuNi)
-200°…690°C
B (PtRh30-PtRh6)
300°…1 820°C
S (PtRh10-Pt)
-50°…1 760°C
R (Pt13Rh-Pt)
-50°…1 740°C
N (Omegalloy)
-200°…1 300°C
L (Fe-CuNi)
-200°…900°C
Instrument accuracy and functionality
Temperature coefficient
50 ppm/°C
Accuracy
±0,2 % of range + 1 digit
(for 10 measur./s)
Accuracy of cold junction measurement
±1,5°C
Rate
5…320 measur./s
Resolution (RTD, T/C)
Cold junction compensation
automatická
Digital filters
floating mean
from 2…30 measurements
exponential mean
from 2…100 measurements
Functions
Tare
designed to reset display on non-zero input signal
Watch-dog
reset after 500 ms
Calibration
at 25°C and 40 % r.h.
Power supply
Power supply
interní sběrnice 5 VDC,24 VDC/max.150 mA
Current draw
< 0,75 W
Mechanical properties
Dimensions
65 x 98 mm
Installation
plug-in card
Operating conditions
Connection
connector terminal board, cable section < 1,5 mm2
Operating temperature
-20°…60°C
Storage temperature
-20°…85°C
Protection class
IP00
El. safety
EN 61010-1, A2
Dielectric strength
2,5 kVAC within 1 min. between bus and inputs
1 kVAC within 1 min. between inputs
Insulation resistance
for polution degree II, measuring cat. III.
input, bus
300 V (ZI), 150 V (Di)*
input, input
150 V (ZI), 100 V (Di)*
EMC
EN 61326-1
Seismic capacity
IEC 980: 1993, par.6
Images
Connection

User manuals

File nameFile typeVersionLanguageDownload
Návod OMR700_IN04
Operating instrucitons OMR700_IN04
PDF
2019.2
Download
Show all ↓Hide ↑